Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/22/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FEEDER TAP GROUNDS TO BE SIZED PER 250 122 6 2) BORDING OF RACEWAYS TO BE PER 514.16.501.30 3) NEED TO POST BOND TO GET POWER RELEASED |
|
| 03/02/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND SOFFITS |