Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T09CM01698
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2010 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. BLDG SLAB AT ELECTRIC ROOM |
|
01/07/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. AT FUEL TANKS |
|
01/05/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NEED SEAL OFFS AT FUEL TANKS AT POINT WHERE CONDUITS EMERGE FROM GRADE-NO JOINTS, UNIONS OR COUPLINGS AT POINT OF EMERGENCE AND SEAL OFF |
|
12/22/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3-4" PVC FROM SES TO TEP XFMR |
|
12/18/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. TO DISPENSERS |
|
12/15/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. TO MONUMENT SIGN AT SOUTH ENTRANCE 2) OK U.G. EXITING FROM UNDER CANOPY TO THE WEST |
|
12/10/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER OF U.G. FOR POLE LIGHTS 2) OK U.G. FOR ? CHANGER, AIR STATION AND MONUMENT SIGNS 3) NOTE: WIREWAYS TO MEET REQUIREMENTS OF NEC 376 |
|
12/04/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER OF U.G. FOR BLDG SLAB 2) OK POLE BASES 8 3) OK U.G. FOR LIGHT POLES AS INDICATED ON PLAN E1 |
|
12/01/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 1ST LEVEL OF UG BLDG SLAB |
|
11/24/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3/4" PVC'S FROM BLDG FOOTING HEADING TO PUMP CANOPY 60' 2) OK 1-4" PVC FROM BLDG FOOTING HEADING TO CANOPY 60' |