Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM01698

Parcel: 141019170


Addresses:

10335 E DREXEL RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM01698

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2010 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/13/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. BLDG SLAB AT ELECTRIC ROOM
01/07/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. AT FUEL TANKS
01/05/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) NEED SEAL OFFS AT FUEL TANKS AT POINT WHERE CONDUITS EMERGE FROM GRADE-NO JOINTS, UNIONS OR COUPLINGS AT POINT OF EMERGENCE AND SEAL OFF
12/22/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3-4" PVC FROM SES TO TEP XFMR
12/18/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. TO DISPENSERS
12/15/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. TO MONUMENT SIGN AT SOUTH ENTRANCE
2) OK U.G. EXITING FROM UNDER CANOPY TO THE WEST
12/10/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK REMAINDER OF U.G. FOR POLE LIGHTS
2) OK U.G. FOR ? CHANGER, AIR STATION AND MONUMENT SIGNS
3) NOTE: WIREWAYS TO MEET REQUIREMENTS OF NEC 376
12/04/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK REMAINDER OF U.G. FOR BLDG SLAB
2) OK POLE BASES 8
3) OK U.G. FOR LIGHT POLES AS INDICATED ON PLAN E1
12/01/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1ST LEVEL OF UG BLDG SLAB
11/24/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3/4" PVC'S FROM BLDG FOOTING HEADING TO PUMP CANOPY 60'
2) OK 1-4" PVC FROM BLDG FOOTING HEADING TO CANOPY 60'