Permit: T09CM01695

Parcel: 136344670


Addresses:

7306 E VICTORIA DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/28/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/17/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMBUSTIBLE CONDENSATE PUMP NOT ALLOWED IN A RETURN PLENIUM
2) PROVIDE A TRAP AS PER INSTALL INSTRUCTIONS
3) PROVIDE AND OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET
4) FAN COIL OVERFUSED
5) TERMINATE CONDENSATE TO THE GROUND
6) SUPPORT COPPER LINE EVERY 6'
7) PROVIDE A BUSHING IN ELECTRIC DISCONNECT
8) FINISH INSTALLING GFI ON ROOF