Permit: T09CM01678

Parcel: 121011270


Addresses:

6026 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) ALL ITEMS ON LIST-OK
07/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) METAL BOXES TO BE GROUNDED
2) MINIMUM 1/4" OF CABLE SHEATH TO ENTER BOXES
3) NEED CONNECTOR OR ROMEX AT ENTRY TO BOXES
4) NEED MINIMUM 6" OF FREE CONDUCTOR LENGTH
5) ALL JUNCTION BOXES TO BE ACCESSIBLE
6) SEAL OPEN KNOCKOUTS IN BOXES
7) OUTDOOR RECEPTS TO BE GFI PROTECTED
8) EXPOSE OLD A/C BRANCH CIRCUIT WIRING TO ENSURE NOT ENERGIZED AND HAS BEE DISCONNECTED
9) RECALL WHEN READY
07/01/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/30/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*