Permit: T09CM01667

Parcel: 12612244E


Addresses:

4525 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/04/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE HIGH EFFICIENCY TAPS AS PER PLANS
PROVIDE LINED BOXES ON CEILING DIFFUSERS AS PER PLANS
PROVIDE A VAPOR BARRIER ON ALL AIR CONDITIONING DUCTS
PROVIDE 2" DUCT LINER IN ALL EXPOSED DUCT ON ROOF
SUPPORT CEILING DIFFUSERS
PROVIDE MIN 1/8" PER FT. SLOPE ON ALL CONDENSATE PIPING. NO DIPS OR SAGS. SUPPORT EVERY 4'