Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE HIGH EFFICIENCY TAPS AS PER PLANS PROVIDE LINED BOXES ON CEILING DIFFUSERS AS PER PLANS PROVIDE A VAPOR BARRIER ON ALL AIR CONDITIONING DUCTS PROVIDE 2" DUCT LINER IN ALL EXPOSED DUCT ON ROOF SUPPORT CEILING DIFFUSERS PROVIDE MIN 1/8" PER FT. SLOPE ON ALL CONDENSATE PIPING. NO DIPS OR SAGS. SUPPORT EVERY 4' |