Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/04/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED K.O. SEAL ON PANEL AT J-BOX 2) NEED LOW VOLTAGE CABLE STRAPPED OR REMOVED 3) NEED MC STRAPPED 1' FROM BOX |
|
| 07/30/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* WM CABLE NOT TO BE USED ON TEE-BAR CEILINGS LOW VOTAGE CABLE TO BE STRAPPED OR REMOVED |