Permit: T09CM01665

Parcel: 13005303G


Addresses:

1915 E 36TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/27/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR TILES-MECHANICAL ONLY
08/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ITEMS 1-5 DATED 8/14/09 HAVE BEEN CORRECTED PROCEED WITH T-BAR INSTALLATION
08/14/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE FLEX CONNECTORS TO UNITS PER PLANS
2 PROVIDE CONICAL TAPS WITH 125 PERCENT FREE AIR OF DESIGN PER PLANS
3) FLEX DUCT NOT TO EXCEED 8' PER PLANS INCLUDING EXHAUST
4) PROVIDE FLEX CONNECTIONS AS DESCRIBED IN PLANS
5) PROVIDE R-8 INSULATION ON ALL DUCT IN VENTED ATTIC SPACE