Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM01665

Parcel: 13005303G


Addresses:

1915 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/03/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH ARC SHIELDS
2) CONDUCTORS IN RACEWAY TO BE COLORED ENTIRE LENGTH-NOT WHITE
3) LABEL TO BE SCREWED TO COVER
4) RECEIVED LETTER FROM ARCHITECT FOR PANEL AND LIGHTS
09/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEPERATE GROUNDS AND NEUTRAL 250.24
2) VERIFY DERATING ON NM CABLE IN RACEWAY 334 & 310.15
3) IF VDV CABELING IS IN WALL CALL FOR INSTALLATION INSPECTION
4) OK TO CLOSE PANEL WALL
08/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ROOMS 6,7,9 & 10
2) OK TO GROUND RODS AND #4