Permit: T09CM01647

Parcel: 99999999A


Addresses:

3915 E LEE ST


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T09CM01647

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2010 SITE - SEWER Approved IVRS - Inspection :*
08/20/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
AIR TESTING FROM UPPER CO TO MH #4 OK
AIR TESTING BETWEEN MANHOLES OK
VAC TESTING OK WITNESSED BY BERT
JUST NEED AUTHORIZATION TO DISCRADE AND TERMINATION OF COS
08/18/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) SEWER PIPING IS COMPLETE
2) SCHEDULE FOR TESTING
08/17/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) HCS CONN AT B2 OK
2) FROM CLEANOUT #5 TO MH AND #4 OK
08/14/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
08/13/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) PIPING FROM MH #3 TO MH #4 LOOKS GOOD, THANKS
2) DON'T FORGET WATER STOPS
08/12/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) PIPING FROM MH 2 TO M3 ALSO COVERED, CALL ME WHEN PIPE IS BEING INSTALLED SO I CAN INSPECT IT
08/11/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) FROM PROP LINE TO MH #2 COVERED, (OK IF INSPECTED BY BERT) INSTALL WATER STOP
08/05/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
1) 2 STICKS OF 8" SDR FROM PUBLIC MH #1 TO PROPERTY. WILL AIR TEST AT LATER DATE