Inspection History: MECHANICAL - FINAL

Permit Number - T09CM01624

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/17/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/14/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSULATE SHEET METAL ELBOWS ON AIR HANDLERS
2) PROVIDE 15 AMP OVERCURRENT PROTECTION FOR FAN COILS
3) PROVIDE BUSHINGS AT DISCHARGE LINES IN FAN COILS
4) PROVIDE TRAPS ON SECONDARY DRAINS
5) SECONDARY DRAINS MUST TERMINATE TO A CONSPICOUS LOCATION
6) INSULATE RETURN PLENIUMS-SEE PLANS
7) PROVIDE A PROTECTIVE COATING ON ARMA FLEX EXPOSED ON ROOF-SEE MANUFACTURERS SPECS