Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/30/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE GREASE FILTERS 2) RELOCATE HEAT SENSOR IN HOOD 3) COMPLETE HOOD AND WALL FLASHING TRIM OUT 4) SEAL M.V.A. DUCT 5) PROVIDE AIR BALANCE REPORT 6) PROVIDE SMOKE CONTAINMENT TEST 7) PROVIDE INTER LOCK TESTS |
|
| 09/29/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST ON TYPE I GREASE DUCT OK 2) OK FOR 1ST LAYER OF WRAP |