Permit: T09CM01618

Parcel: 133400020


Addresses:

555 N PANTANO RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM01618

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AIR BALANCE OK
2) CORRECTIONS HAVE BEEN MADE
3) OK FOR FINAL
10/20/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ERU NOT FUSED CORRECTLY
2) ERU IS BLOCKING DATA PLATE TO A/C UNIT
3) PROVIDE A NEW DATA PLATE
4) ERU IS NOT CONNECTED PROPERLY TO A/C UNIT
5) DO NOT USE DUCT TAPE TO SEAL THIS CONNECTION
6) PROVIDE MINIMUM R8 DUCT LINER IN ALL EXPOSED DUCT ON THE ROOF R4.2 WAS USED
7) PROVIDE A CONDENSATE DRAIN
8) PROVIDE THE INSTALL INSTRUCTIONS FOR ERU
9) PROVIDE AIR BALANCE
10/19/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CALL BACK IN FOR TUESDAY OR WEDNESDAY