Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM01618
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE OK 2) CORRECTIONS HAVE BEEN MADE 3) OK FOR FINAL |
|
10/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ERU NOT FUSED CORRECTLY 2) ERU IS BLOCKING DATA PLATE TO A/C UNIT 3) PROVIDE A NEW DATA PLATE 4) ERU IS NOT CONNECTED PROPERLY TO A/C UNIT 5) DO NOT USE DUCT TAPE TO SEAL THIS CONNECTION 6) PROVIDE MINIMUM R8 DUCT LINER IN ALL EXPOSED DUCT ON THE ROOF R4.2 WAS USED 7) PROVIDE A CONDENSATE DRAIN 8) PROVIDE THE INSTALL INSTRUCTIONS FOR ERU 9) PROVIDE AIR BALANCE |
|
10/19/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL BACK IN FOR TUESDAY OR WEDNESDAY |