Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PANEL DIRECTORY. OPEN PANELS FOR INSPECTION 2) INSTALL WALL PLATES 3) BOXES MORE THAN 1/4" BACK NEED EXTENSIONS 4) CANNOT USE TECH SCREWS FOR GROUND CONNECTION IN MOTOR CONTROLLER 5) CHECK EM AND EXIT LIGHTS, NEED TO BE OPERATIONAL 6) NEED DISCONNECTING MEANS FOR WATER HEATER |