Permit: T09CM01601

Parcel: 12810082B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01601

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/13/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK DROP CEILINGS
09/04/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE ALL LOW VOLTAGE WIRING NOT BEING USED
2) LIGHT FIXTURES TO BE SECURED TO CEILING GROUND
3) CLOSE ALL OPEN JUNCTION BOXES. CLOSE OPEN KNOCKOUTS. FINISH CEILING WORK
4) ENSURE 2 X 4 LIGHT FIXTURES HAVE DISCONNECTING MEANS PER NEC 410.73
08/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK NEW WALLS
2) OK U.G. TO LOW WALL
3) NOTE: ALL 15 AND 20 AMP RECEPTACLES 120X IN KITCHEN AREA TO BE GFI PROTECTED-NO EXCEPTIONS