Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/13/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK DROP CEILINGS |
|
| 09/04/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL LOW VOLTAGE WIRING NOT BEING USED 2) LIGHT FIXTURES TO BE SECURED TO CEILING GROUND 3) CLOSE ALL OPEN JUNCTION BOXES. CLOSE OPEN KNOCKOUTS. FINISH CEILING WORK 4) ENSURE 2 X 4 LIGHT FIXTURES HAVE DISCONNECTING MEANS PER NEC 410.73 |
|
| 08/19/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK NEW WALLS 2) OK U.G. TO LOW WALL 3) NOTE: ALL 15 AND 20 AMP RECEPTACLES 120X IN KITCHEN AREA TO BE GFI PROTECTED-NO EXCEPTIONS |