Permit: T09CM01592

Parcel: 113043310

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/31/2009 ELECTRIC - FINAL Approved
07/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEW T-BAR CEILING AND 2 X 4 LAY IN FIXTURES, ROMEX WIRING METHOD NOT PERMITTED PER 334 NEC. NOT SHOWN ON PLAN CHECK
2) ALSO SERVICE EQUIPMENT (DISC SW) NOT RATED FOR OUTDOOR USE, SERVICE NOT GROUNDED AND BONDED. SERVICE RISER NOT TO CODE. UPGRADE SERVICE, REVISE PLAN AS PER NOT #1 230, 250 NEC.