Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | ELECTRIC - FINAL | Approved | ||
| 07/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEW T-BAR CEILING AND 2 X 4 LAY IN FIXTURES, ROMEX WIRING METHOD NOT PERMITTED PER 334 NEC. NOT SHOWN ON PLAN CHECK 2) ALSO SERVICE EQUIPMENT (DISC SW) NOT RATED FOR OUTDOOR USE, SERVICE NOT GROUNDED AND BONDED. SERVICE RISER NOT TO CODE. UPGRADE SERVICE, REVISE PLAN AS PER NOT #1 230, 250 NEC. |