Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01591
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2009 | ELECTRIC - FINAL | Approved | RED LINES OK | |
09/10/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PREVIOUS CORRECTION-ITEMS CORRECTED 2) NEED TO REVISE PLANS BASED ON RED LINE DRAWINGS. REVISED PLANS TO GO BACK THROUGH PLAN REVIEW |
|
09/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK NEW RECEPTACLES ADDED PER PLANS 2) NEED PROPER WORKING CLEARANCES IN FRONT OF PANELS NEC 110.26 3) ONE OF THE SERVICES HAD IT'S GROUNDING ELECTRODE CONDUCTOR CUT AND STOLEN. NEED TO REPAIR OR INSTALL NEW GROUNDING ELECTRODE SYSTEM 4) SEAL ALL OPEN KNOCKOUTS |