Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/02/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE NEW RECEPTS WITH NO POWER 2) NEED HANDLE TIE ON CIRCUITS FEEDING WORK STATIONS 3) EM LIGHTING TO BE PER NEC 700.12 4) SOME EM LIGHTS NOT WORKING WHEN TESTED 5) NEED UPDATED PANELS SCHEDULES 6) CHECK BRASS COVER PLATES FOR FLOOR RECEPTS ARE BONDED TO EQUIPMENT GROUND 7) HAVE OPEN JUNCTION BOXES OF WIRE HANGING. NEEDS TO BE CLOSED UP AND MADE SAFE 8) NEED TO PROVIDE RED LINE DRAWINGS FOR AS-BUILTS TO BE SUBMITTED FOR APPROVAL AT COMPLETION OF PROJECT |