Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM01579

Parcel: 11012007B


Addresses:

5151 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
09/18/2009 PLUMBING - PROGRESS Approved
09/17/2009 PLUMBING - PROGRESS Not ready for Inspection ALL FIXTURES REQUIRE A DIRECT CONN EXCEPT AS SPECIFIED IN CHPT 8. ONLY THE SANITIZE COMP MAY DRAIN INDIRECTLY. PIPE 2 COMPATTMENTS DIRECTLY WITH ONLY 1 COMP TO FS PER PLAN. HAND SINK IS MISSING ITS VENT (AA6) ALSO PROVIDE APPROVED TRANSITION COUPLING AT CL TO PL. HS MISSING CLEAN OUT.
09/16/2009 PLUMBING - PROGRESS Approved IVRS - Inspection :*
09/03/2009 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
PROVIDE ACCESS PANELS FOR CLEANOUTS AND AAVS
08/24/2009 PLUMBING - PROGRESS Denied 1) REQUIRE APPROVED RECEPTOR FOR ICE MAKER. SEE OTHER ACTIVITY AND PLAN FOR WORK IN THAT LOCATION
2) COURTESY CALL TO WAYNE SWAN