Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T09CM01579
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
08/26/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HORIZONTAL WET VENTING IS NOT PERMITTED 2) INSTALL PER PLAN 3) PROVIDE SOLVENT WELD FITTINGS 4) REPAIR COUPLING IS NOT WARRANTED |
|
08/24/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STILL NOT PER PLAN, ALSO REMOVE CONSTRUCTION DEBRIS FROM DITCH 2) PROVIDE AN APPROVED RECEPTOR (FS) FOR ICE MAKER DRAIN NOW THAT THE FLOOR HAS BEEN OPENED UP FOR NEW WORK 3) NO PLAN REVISION IS REQUIRED, BUT DO HAVE PLANS FOR THIS ACTIVITY ON SITE AND CALL FOR INSPECTIONS ON BOTH ACTIVITIES |
|
08/20/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT INSTALLED PER PLAN PROVIDE A DIRECT CONNECTION FOR 3 COMP SINK PER PLAN PROVIDE DRAINAGE FITTING ON VENT BELOW FIXTURE FLOOD L YOUR PLAN DOES NOT APPEAR TO ADDRESS THE PROBLEM THAT YOU HAD PROVIDING AN AIR CAP ON YOUR GRAVITY DRAIN FROM THE ICE MAKER VERBAL WARNING GIVEN TO; CAP OPEN DRAIN AT HAND SINK! HAND SINK IS NOT EXISTING UNTIL T08CM02730 HAS HAD FINAL APPROVAL |