Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/14/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/17/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BELL BOX ON ROOF TO BE SECURED/SUPPORTED
2) TIGHTEN EMT FITTINGS
3) STRAP/SECURE EMT FOR ROOF TOP RECEPTACLE
4) ROOF TOP RECEPTACLE TO BE GFI PROTECTED
5) RECEPTACLES EXPOSED TO WEATHER TO HAVE IN USE COVER (BUBBLE COVER)
6) ALL STRANDS OF NEUTRAL CONDUCTOR TO BE UNDER TERMINAL
7) COMPLETE ITEM #8
8) HAVE 100 PERCENT COMPLETE FOR NEX INSPECTION TO AVOID REFEE
08/03/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BREAKERS LISTED FOR USE IN GE PANEL
2) BLANK OPEN BREAKER POSITION
3) NEED PANEL DIRECTORY
4) ONE NEUTRAL PER TERMINAL IN PANEL
5) PROPERLY IDENTIFY EQUIPMENT GROUND ALONG ENTIRE LENGTH
6) INSTALL CIRCUIT FOR ROOF TOP RECEPTACLE CANNOT ? 40 AMP A/C CIRCUIT
7) NEED PROPER WORKING CLEARANCE IN FRONT OF DISCONNECT
8) USE STAINLESS HARD WIRE TO STRAP PVC CONDUIT AND USE ? RESISTANT WOOD
07/13/2009 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) REMOVE PAINT AT GROUND CLAMP CONNECTION ON GAS PIPE
2) GROUND RODS TO BE MINIMUM 6' APART
3) INSTALL PROTECTIVE BUSHING AROUND WIRES ENTERING BACK OF PANEL
4) PARTIAL APPROVAL TO GET POWER RESTORED BECAUSE OF POWER KILL
5) RECALL WHEN WORK COMPLETE