Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T09CM01550
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2009 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
11/02/2009 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) SAN TEE SHOWER DRAIN TO HORIZ 3" SEWER MUST BE A COMBO FITTING 2) I THINK TRAP ARM WILL BE OVER 42" LIMIT TRAP WIER TO VENT INLET 3) NOTE: PLAN SHOWS SEWER UNDER BLDG, MY ADVICE IS TO DO IT THAT WAY TO AVOID ROOF DRAINAGE FILLING AND FOLLOWING SEWER TRENCH MAKING FOOTING SOIL WET |