Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM01518
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) TESTED DUCT SMOKE DETECTOR |
|
02/10/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FOR TILES IN CLEAN ROOM |
|
01/29/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS NEED TO BE RE-LOCATED |
|
01/20/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 100 PSI HYDRSTATIC TEST ON ALL REMAINING PIPING OK 2) OK TO INSULATE |
|
12/07/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/17/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DUCT SUPPORT NOT PER PLANS, PROVIDE ENGINEERS APPROVAL ON ALL CHANGES TO PLANS |
|
09/21/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND FROM CENTRAL PLANS RISER TO BLDG 2) RISER PRESSURE TEST 100 + PSI 3) OK TO BACKFILL |
|
08/24/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 4" CONDENSOR WATER SUPPLY AND RETURN RISER ONLY |
|
08/21/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |