Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ENGINEERING OFFICE #2 2) OK BREAKROOM 3) RECALL FOR INSPECTION OF REWIRE OF VANDALIZED ELECTRIC |
|
| 11/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS EXCEPT, BREAKROOM AND MECH ROOM |
|
| 11/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS MECH ROOM 2) 2" VENT IN DEDICATED PANEL SPACE 110-26 NEC |
|
| 10/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 GROUND RODS AND 3/0 PER DAN'S INSTRUCTIONS |
|
| 08/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FEEDER CONDUITS TO DIST. GEAR AT NEW BLDG AND STUB OUTS FOR EAST PARKING AREA |
|
| 08/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BELOW BLDG SLAB CONDUITS |