Permit: T09CM01503

Parcel: 11307042A


Addresses:

2965 N CAMPBELL AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/10/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/09/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
09/03/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ALL HOOD SYSTEMS OK, OK FOR FIRE SUPPRESSION SYSTEM TEST. SEE BLDG. INSPECTOR FOR TEMP C OF O

1. EXISTING UNIT IS SUPPORTED ON ROOF WITH 5 GAL. PAINT CAN, PROVIDE PROPER/APPROVED SUPPORT
2. NEW UNIT IS OUT OF LEVEL CAUSING CONDENSATE TO DRAIN UPHILL, UNIT MUST BE LEVEL
3. ALL SERVICEABLE EQUIPMENT WITHIN 10' OF ROOF EDGE MUST HAVE A RAILING A MIN. OF 42" HIGH AND EXTENDING 36" IN EACH DIRECTION OF SAID EQUIPMENT (THE NEWLY INSTALLED TYPE 1 EXHAUST FAN IS TOO CLOSE TO EDGE)
09/02/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO CAPTURE AND CONTAINMENT TEST
2) NEED TO TEST HEAT SENORS
3) AIR BALANCE OK
4) EXTEND SEWER VENTS 2' ABOVE EVAP COOLER
5) CAP OFF CONDENSATE VENTS
08/31/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) VENT ON CONDENSATE TRAP NEEDS TO BE RELOCATED DOWNSTREAM OF TRAP
2) SMOKE TEST ON REMAINDER OF GREASE DUCTS OK
3) NO FLEX DUCT WITHIN 18" OF TOP OF HOOD ALLOWED
08/26/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/03/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*