Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/03/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ALL HOOD SYSTEMS OK, OK FOR FIRE SUPPRESSION SYSTEM TEST. SEE BLDG. INSPECTOR FOR TEMP C OF O 1. EXISTING UNIT IS SUPPORTED ON ROOF WITH 5 GAL. PAINT CAN, PROVIDE PROPER/APPROVED SUPPORT 2. NEW UNIT IS OUT OF LEVEL CAUSING CONDENSATE TO DRAIN UPHILL, UNIT MUST BE LEVEL 3. ALL SERVICEABLE EQUIPMENT WITHIN 10' OF ROOF EDGE MUST HAVE A RAILING A MIN. OF 42" HIGH AND EXTENDING 36" IN EACH DIRECTION OF SAID EQUIPMENT (THE NEWLY INSTALLED TYPE 1 EXHAUST FAN IS TOO CLOSE TO EDGE) |
|
| 09/02/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO CAPTURE AND CONTAINMENT TEST 2) NEED TO TEST HEAT SENORS 3) AIR BALANCE OK 4) EXTEND SEWER VENTS 2' ABOVE EVAP COOLER 5) CAP OFF CONDENSATE VENTS |
|
| 08/31/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) VENT ON CONDENSATE TRAP NEEDS TO BE RELOCATED DOWNSTREAM OF TRAP 2) SMOKE TEST ON REMAINDER OF GREASE DUCTS OK 3) NO FLEX DUCT WITHIN 18" OF TOP OF HOOD ALLOWED |
|
| 08/26/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/03/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |