Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/02/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL VENTS WITHIN 10' OF AIR INTAKE TO BE EXTENDED. FURNACES NOT PERMITTED 2) PAINT PLASTIC 3) FINISH INSULATING HOT AND COLD AT WATER HEATER 4) SINKS REQUIRE CLEANOUTS 5) 3 COMPARTMENT SINK TO BE DIRECTLY CONNECTED TO SANITARY SEWER 6) ANSUL VALVE NOT LABELED 7) RESTRAINTS NOT CONNECTED AT ? GAS APPLIANCES 8) HAND SINK TO BE DIRECTLY CONNECTED TO SANITARY SEWER 9) SEE 1.09 PLUMBING NOTES-STERILIZATION |
|
| 08/31/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE VACUUM BREAKERS AT AIR HOSE BIBS AND MOP SINK 2) COMPLETE ALL SINK INSTALLS 3) COMPLETE ALL EQUIPMENT INSTALLS 4) PROVIDE BACKFLOW CERTS AND TERMINATE AIR GAP FITTING TO DRAINS 5) PROVIDE PEMPERING AT PUBLIC USE LAVS PER P2.0 6) SEE BLDG INSPECTION REPORT FOR KNEE CLEARANCE FOR LAV |
|
| 08/03/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |