Permit: T09CM01494

Parcel: 13101002L


Addresses:

2400 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01494

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2009 ELECTRIC - FINAL Approved ENGINEER ACCEPTANCE TEST FROM GLHN ACCEPTED AND FILED.

ORIGINAL UL LISTING FOR MUSCO POLES AND LIGHTS REESTABLISHED THROUGH CERTIFICATION PROVIDED BY THEIR ENGINEER. ALSO FILED.
07/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/01/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER FROM GLHN FOR ACCEPTANCE OF TEST RESULTS BY SELLERS AND SONS
2) ALSO MEGGER READINGS BY MUSCO CO. OF HARNESS REPLACEMENT REVIEWED BY ELECTRICAL ENGINEER (JOHN LUNDGREN P.E.) FOR ACCEPTANCE
06/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SELLERS & SONS CONTR.

RESUME WORK ON LIGHT POLES AND ELEC. EQUIP.
ALSO, RE-LAMPING AS NECESSARY - WILL REPLACE FEEDERS TO LIGHT POLE #C1 AT FIELD "A" DUE TO UNACCEPTABLE READING OF INSULATION VALUE WHEN TESTED. ALSO, FOUND RODENT OR INSECT DAMAGE TO WIRING IN PARKING LOT
POLE J-BOXES (ANTS EATING INSULATION OF CONDUCTORS) PARKS & REC. TO EXTERMINATE AS NECESSARY. ALSO, DID INSPECTION AT CELL TOWER ON SAME PROPERTY TODAY, DIFFERENT CONTR. T09CM01304
06/17/2009 ELECTRIC - FINAL Partial Approval CHECK ON PROGRESS. SELLERS STILL CLEANING EQUIP.
ALSO, REPLACED 480V X-FORMER DISCONNECT THAT HAD A BROKEN HANDLE (ON-OFF) - FOUND MONEY & TOY IN X-FORMER AT BALLFIELD AREA. INSPECTOR WALKED WITH SELLERS (CONTR.) CHECKED GROUNDING AT N.E.BALLFIELD LT. POLES
SELLERS TO CHECK ALL POLES, VERIFY GROUND CONNECTIONS INTACT, WILL BEGIN MEGGER TESTING ON FRIDAY 6/19/09
06/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LIGHT POLE REPAIRS
SELLERS & SONS INC. CONTRACTED BY C.O.T FOR PERFORMING ELECTRICAL REPAIRS AS NECESSARY FOR A SAFE AND CODE COMPLIANT ELECTRICAL SYSTEM FOR BALLFIELD LTG. AT THIS LOCATION.

SELLERS & SONS WILL BE OPENING ELECTRICAL EQUIP. TO CLEAN, TEST WIRING USING MEGGER, RE-TORQUE FEEDERS, CHECK GROUNDING, SPLICES, TO INSURE A SAFE OPERATING ELECTRICAL SYSTEM FOR BALL PARK LTG. AT THIS LOCATION

"MUSCO CO." WILL VERIFY POLE WIRING AT BALLAST BOXES UP TO LAMPS BY MEGGER TESTING CONDUCTORS.

RESULTS OF TESTING BY BOTH PARTIES TO BE SUBMITTED TO AN ELECTRICAL ENGINEER FOR REVIEW AND APPROVAL.

COPIES TO ELEC. INSPECTOR (DSD)

ELEC. INSPECTOR WALKED AREA WITH PHIL (SELLERS SUPT)
LOOKED AT EQUIPMENT THAT WAS OPENED AT THIS TIME
TO RESUME TOMORROW
06/12/2009 ELECTRIC - FINAL Partial Approval ELEC. INSPECTOR (DAN SANTA CRUZ) ARRIVED ON JOB SITE EARLY AM "MUSCO" IN PROCESS OF REPLACING WIRING HARNESS TO 16 LT POLE UPON INSPECTION IT WAS OBSERVED THAT THERE WAS DAMAGE TO INSULATION DUE TO RUBBING ON POLE. KEN SUGGESTED THIS COULD HAVE BEEN DONE DURING EXTRACTION OF HARNESS FROM POLE.

THERE WAS ALSO PREVENTATIVE MAINT. BY "MUSCO" AT SOCCER FIELD. INSPECTOR NOTICED UPON INSPECTION OF
LT. POLE AT SOUTH OF FIELD THAT THERE WAS NO EQUIP. GROUND TERMINATED OR RUN TO TERMINATION CABINET ON POLE. THIS WILL BE ADDRESSED PER KEN. IT IS ADVISED THAT ALL BALL FIELDS NOT BE USED FOR PUBLIC (ACCESS) UNTIL ELECTRICAL ISSUES BE RESOLVED.

ELEC. CONTR. TO BE ON SITE MONDAY 6/15/09 TO ASSESS GROUNDING AND UNGROUNDED CONDUCTOR EVAL.

PLEASE HAVE CONTR. CONTACT INSPECTOR DAN SANTA CRUZ
06/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ELEC. INSP. MET WITH MUSCO CO., KEN, FRED (PARKS & REC)
AM TO DISCUSS REPAIRS & ACTION TO BE TAKEN TO CORRECT ELECTRICAL ISSUES WITH BALL PARK LTG. "MUSCO" TO STAGE TOMORROW 6/12/09 WILL BEGIN REPLACING WIRING HARNESS FOR 16 POLES AT EAST BASEBALL FIELDS. KEN WILL DECIDE HOW TO ADDRESS PERFORMANCE TESTING OF EXISTING WIRING FROM LT. POLES BACK TO SOURCE AS REQUESTED BY ELEC. INSPECTOR - ALSO, REQUESTED WAS THAT ALL NEW WIRING HARNESSES TO BE MEGGER TESTED AFTER INSTALLATION TO ENSURE QUALITY ASSURANCE OF CONDUCTORS. LIGHT POLES ARE UL LISTED ASSEMBLY