Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO SANITARY VENT CAN SERVE AS A DRAIN (RELIEF DRAIN CANNOT TERMINATE INTO VENT PIPE ON ROOF) SHOULD TERMINATE 6" TO 24" FROM FINISH GRADE OR JUST ABOVE ROOF SURFACE IF OK WITH OWNER 2. TEMPERATURE & PRESSURE RELIEF ON TANK CANNOT GO UP THRU ROOF - SEE NOTE #2 FROM 8/7/09 INSPECTION AND COMPLY PETITION OF APPEAL AVAILABLE @ 201 N STONE AND NEEDS TO BE ON SITE (SIGNED) 3. ZIP TIES ARE NOT APPROVED SUPPORTS FOR TANKS |
|
| 08/07/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |