Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* 1) PROVIDE CONDENSATE CONNECTIONS TO A/C UNITS 2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 3) PERMANENTLY I.D. ALL EQUIPMENT 4) RELOCATE LARGE CONDENSOR OR PROVIDE A DATA PLATE IN AN ACCESSIBLE LOCATION 5) NEED AIR BALANCE, CAPTURE AND CONTAINMENT AND HEAT SENSOR TEST, DUCT SMOKE DETECTOR TEST |
|
| 11/03/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 2ND LAYER FIRE WRAP OK BOTH HOODS, FRONT HOOD STILL NEEDS ACCESS DOOR 2) SEAL M.V.A DUCT |
|
| 10/26/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) ROOF TOP PERMANENT LADDER SHALL EXTEND DOWN TO GRADE OR FLOOR LEVEL SECT. 306.5 IMC 2) COMPLETE 1ST LAYER, OK TO INSTALL 2ND LAYER |
|
| 10/22/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCTS 2) OK FOR 1ST LAYER OF FIRE WRAP |