Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) MAU DUCT BLOCKING ACCESS TO CLEANOUT DOOR 2) CANNOT CONFIRM DUCT ON RIGHT SIDE OF LARGE HOOD, CAN BE CLEANED FROM THIS ONLY CLEANOUT 3) MAY NEED TO ADD ANOTHER DOOR 4) REMOVE INSULATION FROM DOOR |
|
| 12/09/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSULATE MAKE UP AIR DUCT AS PER PLAN 2) INSTALL FLEX DUCTS PER DETAIL 106 ON PLANS 3) FIRE WRAP NOT BANDED CORRECTLY 4) OVERLAPS NOT CORRECT 5) PROVIDE INSTALL INSTRUCTIONS FOR CLEANOUT DOOR |