Permit: T09CM01465

Parcel: 12706012A


Addresses:

4701 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/16/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) MAU DUCT BLOCKING ACCESS TO CLEANOUT DOOR
2) CANNOT CONFIRM DUCT ON RIGHT SIDE OF LARGE HOOD, CAN BE CLEANED FROM THIS ONLY CLEANOUT
3) MAY NEED TO ADD ANOTHER DOOR
4) REMOVE INSULATION FROM DOOR
12/09/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSULATE MAKE UP AIR DUCT AS PER PLAN
2) INSTALL FLEX DUCTS PER DETAIL 106 ON PLANS
3) FIRE WRAP NOT BANDED CORRECTLY
4) OVERLAPS NOT CORRECT
5) PROVIDE INSTALL INSTRUCTIONS FOR CLEANOUT DOOR