Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01460
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/31/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND HARD LIDS |
|
| 07/28/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MC TO BE SUPPORTED PER NEC. 12" AT TERM & 6' INTERVALS-THRU BORED HOLES OK. 330 NEC 2) NAIL PLATES REQUIRED WHERE LESS THAN 1 1/4" TO STUD FACE 300.4 NEC. 3) CEILING NOT APPROVED 4) BE ADVISED, MORE THAN 30 CURRENT CARRING CONDUCTORS IN EXISTING GUTTER MUST BE DERATED PER 310.15 NEC AND 366.22 NEC. |