Permit: T09CM01456

Parcel: 141340370

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01456

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT TO BE OFF AND OPENED FOR INSPECTION
2. INVERTER INDICATING GROUND FAULT
3. INSTALL #8 GROUNDING ELECTRODE CONDUCTOR PER PLANS
4. INSTALL LABELING PER PLANS AND NEC 690
5. INSTALL BONDING BUSHING AROUND REDUCING WASHERS OR INSTALL REDUCING WASHERS PER INSTRUCTIONS
6. STRAP EMT WITHIN 3' OF BOXES
7. RECALL WHEN READY