Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01456
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT TO BE OFF AND OPENED FOR INSPECTION 2. INVERTER INDICATING GROUND FAULT 3. INSTALL #8 GROUNDING ELECTRODE CONDUCTOR PER PLANS 4. INSTALL LABELING PER PLANS AND NEC 690 5. INSTALL BONDING BUSHING AROUND REDUCING WASHERS OR INSTALL REDUCING WASHERS PER INSTRUCTIONS 6. STRAP EMT WITHIN 3' OF BOXES 7. RECALL WHEN READY |