Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01448
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS 200.7 2) OK RECEPTION AREA |
|
| 08/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FRONT RECEPTION AREA OK ONLY, EXAM ROOM WIRING OK 2) NEED LOW VOLTAGE BUSHINGS |
|
| 07/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) EXAMS ROOMS HAVE BEEN RE-WIRED OK |
|
| 07/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) THERAPY ROOM AND HALLWAY-OK 2) EXAM ROOMS NEED TO BE REWIRED |
|
| 07/15/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/13/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE VERIFY EXISTING WIRING METHODS FOR EXAM ROOMS 2) NM CABLE WAS NEVER APPROVED AS A WIRING METHOD FOR HEALTHCARE FACILITIES 3) DUE TO THE NATURE OF USE FOR THESE ROOMS ARTICLE 517.13 IS NEEDED 4) IF ROOMS ARE NOT EXAM, REVISE PLANS TO STATE AS SUCH 5) FINISH PREVIOUS ITEMS |
|
| 07/09/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED MC STRAPPED USING PROPER ONE HOLE STRAPS FOR MC AND MC HAS TO BE 1 1/4 FROM EDGE OF STUD 2) NEED A/C CABLE FOR EXAM ROOMS UNLESS EXISTING IS IN EMT 3) NEED TO PUT MC PARALLEL WITH WALL NOT THE STUD |