Permit: T09CM01448

Parcel: 11015125B


Addresses:

5655 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01448

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2009 ELECTRIC - INTERMEDIATE Approved
08/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS 200.7
2) OK RECEPTION AREA
08/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FRONT RECEPTION AREA OK ONLY, EXAM ROOM WIRING OK
2) NEED LOW VOLTAGE BUSHINGS
07/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EXAMS ROOMS HAVE BEEN RE-WIRED OK
07/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) THERAPY ROOM AND HALLWAY-OK
2) EXAM ROOMS NEED TO BE REWIRED
07/15/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/13/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PLEASE VERIFY EXISTING WIRING METHODS FOR EXAM ROOMS
2) NM CABLE WAS NEVER APPROVED AS A WIRING METHOD FOR HEALTHCARE FACILITIES
3) DUE TO THE NATURE OF USE FOR THESE ROOMS ARTICLE 517.13 IS NEEDED
4) IF ROOMS ARE NOT EXAM, REVISE PLANS TO STATE AS SUCH
5) FINISH PREVIOUS ITEMS
07/09/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED MC STRAPPED USING PROPER ONE HOLE STRAPS FOR MC AND MC HAS TO BE 1 1/4 FROM EDGE OF STUD
2) NEED A/C CABLE FOR EXAM ROOMS UNLESS EXISTING IS IN EMT
3) NEED TO PUT MC PARALLEL WITH WALL NOT THE STUD