Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 09/16/2009 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNDERGROUND GAS PIPING TO BE MINIMUM 12" OF COLOR ABOVE GROUND PIPING TO BE MINIMUM 3 1/2" ABOVE GROUND. ALL UNDERGROUND PIPING FITTINGS & TOOL MARK SAME BE PRINTED THEN TAPED TO ACHIEVE 40 MIL THICKNESS OF WRAP. SECURE GAS PIPING AT DROP BY OCD ? SERVICE AREA. INDUSTRIAL APPROVED GAS SHUT OFF VALVE AT ENTRANCE TO BUILDING PER PLAN. PROVIDE 1" CLEARANCE FROM (ROOF MECHANICAL) (COMBUSTIBLES) FROM VENT FROM WATER HEATER. |
|
| 09/15/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |