Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM01381
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/26/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH NOTE #2 FROM INSPECTION ON 7/27/09 2) FIXTURES TO BE SECURED TO CEILING GRID IS USING CLIPS THEY NEED TO BE EFFECTIVE 3) STRAP MC CABLE TO WITHIN 12" OF BOXES 4) INSTALL OCCUPANCY SENSORS PER PLAN 5) INSTALL SIESMIC WIRES ON EXITS 6) HALL FIXTURES TO BE 2 32 W T8 NOT 3 32W T8 7) RECALL AFTER CORRECTIONS HAVE BEEN MADE |