Permit: T09CM01381

Parcel: 14117690C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM01381

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/26/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH NOTE #2 FROM INSPECTION ON 7/27/09
2) FIXTURES TO BE SECURED TO CEILING GRID IS USING CLIPS THEY NEED TO BE EFFECTIVE
3) STRAP MC CABLE TO WITHIN 12" OF BOXES
4) INSTALL OCCUPANCY SENSORS PER PLAN
5) INSTALL SIESMIC WIRES ON EXITS
6) HALL FIXTURES TO BE 2 32 W T8 NOT 3 32W T8
7) RECALL AFTER CORRECTIONS HAVE BEEN MADE