Permit: T09CM01381

Parcel: 14117690C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01381

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/31/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CEILINGS
07/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND HARD LIDS
2) CONDUIT SIZE PER PLANS TO BE 2", FOR WIRE SIZE SHOWN NEED MINIMUM 1 1/2". PROVIDE LETTER FROM ENGINEER FOR ANY CHANGES IN FEEDER SIZE AND CONDUIT SIZE