Permit: T09CM01376

Parcel: 111060210


Addresses:

2946 N WINSTEL BL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/02/2009 BUILDING - FINAL Approved IVRS - Inspection :*
09/30/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) APPEAL MUST BE APPROVED BY CITY OF TUCSON BLDG OFFICIAL
09/25/2009 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) WATER HEATER NOT ALLOWED TO BE CORD AND PLUG CONNECTED
2) REVISE AND RECALCULATE ROOF LOAD FOR NEW MODULE LAYOUT
3) LABEL AT MAIN PANEL TO BE PER 690.17, ALSO AT A/C DISCONNECT
4) CHECK PRESSURE VALVE ON ROOF-RUN DOWN TO TERMINATE 6" FROM GRADE