Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE OK 2) OK FOR FINAL |
|
| 11/09/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 11/06/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE DISCONNECTS FOR WALK IN FAN COILS 2) PROVIDE ROOF JACKS AT REFER LINE PENTRATIONS 3) PROVIDE AIR BALANCE REPORT 4) PROVIDE EXTENSION ON EXHAUST FAN 5) PERMANENTLY ID EQUIPMENT ON ROOF 6) PAINT EXPOSED PVC WITH LATEX PAINT 7) DUCT SMOKE DETECTOR NOT SHUTING DOWN A/C FAN 8) CAPTURE AND CONTAINMENT TEST OK 9) HEAT SENSOR TEST OK |