Permit: T09CM01367

Parcel: 11005318D

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/30/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) CEILINGS AND WALLS OK
06/26/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) JUNCTION BOXES TO BE ACCESSIBLE-CANNOT BURY IN WALL
2) SUPPORT M/C WITHIN 12" OF BOXES
3) BOX OVER FILLED
4) USE APPROVED CONNECTORS FOR M/C
5) NOTE: EXISTING RECEPTACLES TO BE AS PER 517.13
6) EXIT LIGHTS TO BE PER 700.12 (F)
7) FILL UNUSED OPENINGS IN LIGHT BOXES
06/24/2009 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled