Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) CEILINGS AND WALLS OK |
|
| 06/26/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) JUNCTION BOXES TO BE ACCESSIBLE-CANNOT BURY IN WALL 2) SUPPORT M/C WITHIN 12" OF BOXES 3) BOX OVER FILLED 4) USE APPROVED CONNECTORS FOR M/C 5) NOTE: EXISTING RECEPTACLES TO BE AS PER 517.13 6) EXIT LIGHTS TO BE PER 700.12 (F) 7) FILL UNUSED OPENINGS IN LIGHT BOXES |
|
| 06/24/2009 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled |