Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM01365

Parcel: 209170040


Addresses:

6505 S SANDARIO RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/10/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
06/07/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) LABEL LIEBERT DISCONNECTS
2) BOND DISCONNECT ENCLOSURES
3) BOND BUSHING OVER 250V
4) LABEL PANEL
5) IDENTIFY GROUNDING EQUIPMENT CONDUCTORS AT WELL HEAD