Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2010 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/24/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE WAITING ON GFI PAPERWORK REPORT |
|
| 03/11/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) BONDING IN SERVICE CT CAN TO BE TO ENCLOSURE AND PER 250.102 2) ONLY ONE CONDUCTOR PER LUG 3) NEED GROUNDED CONDUCTOR BROUGHT TO SERVICE MAINS 250.249(C) 4) NEED GFI TEST PER 230.95 5) NEED LETTER OF TORQUE FOR SERVICE MCC'S 6) ANGLE PULL TO BE PER 312.28 GX 7) WILL NEED COPY OF LOCKOUT/TAGOUT ON SITE |