Permit: T09CM01358

Parcel: 11308011A


Addresses:

3128 N 1ST AV

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/02/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/01/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/31/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/11/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE MAIN SALES FLOOR OK TO COVER
2) PROVIDER AUDIO/VISUAL ALARM ON SMOKE DETECTOR PRIOR TO FINAL
07/06/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) COMPLETE DUCT SEAL
2) INSULATE CONDENSATE PIPING
3) PROVIDE HEAD PRESSURE TEST ON CONDENSATE PIPING
4) PROVIDE APPROVED TAPS FOR DUCT TAKE OFFS