Permit: T09CM01358

Parcel: 11308011A


Addresses:

3128 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01358

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/08/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTOR TO COMPLETE, BUTTON UP (SEAL OFFS) IN ELECTRIC ROOM
09/07/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EXPOSED CONDUIT FOR SIGN POWER TO BE SCHEDULE 80 OR STEEL (SUBJECT TO ? DAMAGE)
09/02/2010 ELECTRIC - FINAL Partial Approval ALL METAL RACEWAYS TO BE BONDED PER 514.16 & 501.30 (AT DISPENSERS)

BUSHINGS PER 352.46

SECOND RETURN INSPECTION FOUND NOT ALL SEALOFFS HAD CHICO SEALANT.

WITNESSED SEALANT PLACEMENT. ALL OK EXCEPT CONDUIT LOOSE AT DISPENSER #13.
09/01/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ROOF
2) NEED TO INSPECT CANOPY
3) SEAL SEAL OFFS
4) CALL FOR TANK INSPECTIONS UNDER TANK PERMIT