Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01358
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/08/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONTRACTOR TO COMPLETE, BUTTON UP (SEAL OFFS) IN ELECTRIC ROOM |
|
09/07/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EXPOSED CONDUIT FOR SIGN POWER TO BE SCHEDULE 80 OR STEEL (SUBJECT TO ? DAMAGE) |
|
09/02/2010 | ELECTRIC - FINAL | Partial Approval | ALL METAL RACEWAYS TO BE BONDED PER 514.16 & 501.30 (AT DISPENSERS) BUSHINGS PER 352.46 SECOND RETURN INSPECTION FOUND NOT ALL SEALOFFS HAD CHICO SEALANT. WITNESSED SEALANT PLACEMENT. ALL OK EXCEPT CONDUIT LOOSE AT DISPENSER #13. |
|
09/01/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOF 2) NEED TO INSPECT CANOPY 3) SEAL SEAL OFFS 4) CALL FOR TANK INSPECTIONS UNDER TANK PERMIT |