Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE INSPECTION ITEMS FORM 9/21/09 |
|
| 09/21/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES APPLY TO BOTH ADDRESSES ON THIS PERMIT: 1) GROUND CLAMP LISTED FOR ONE WIRE TERMINATION 2) HAVE CUT STRANDS ON WIRES TERMINATED IN PANELS 3) SPLIT BOLT CONNECTOR LISTED FOR 2 WIRE TERMINATION |
|
| 07/31/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES #2146 ------------------------------------------------------------------------------------------------- 1) SEE NOTES FROM INSPECTION 7/9/09 2) COVERS DO NOT OPEN PROPERLY, CONDUITS AT TOP OF PANELS TO CLOSE TO COVER |
|
| 07/09/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PERMITS FOR NEW ROOF TOP A/C UNITS 2) EXPOSE GROUND RODS 3) BOND GAS PIPING 4) SEAL OPEN KNOCKOUTS 5) STRAP EMT WITHIN 3' OF CONNECTIONS 6) GROUNDS AND NEUTRALS TO BE SEPERATE IN PANEL 7) CANNOT RUN FEEDERS FOR OTHER PANELS THRU PANEL 8) INDENTIFY WHITE CONDUCTORS USED AS PHASE CONDUCTORS 9) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANELS 10) BOND AROUND ? WASHERS 11) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT 12) ALL NEW ELECTRIC WORK TO BE PERMITTED AND INSPECTED |