Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM01348
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CONDENSATE PIPING CANNOT BE SUPPORTED FROM COMM. WIRES 2) INSULATE S/A DUCT WHERE IT CROSSES EXHAUST DUCT IN LOBBY 3) PROVIDE REQUIRED AMOUNT OF SCREWS IN EXHAUST DUCT 4) PROVIDE RED LINE DRAWINGS OF CHANGES OF DUCT ROUTING PRIOR TO FINAL |