Permit: T09CM01348

Parcel: 12701005D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/29/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/27/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CONDENSATE PIPING CANNOT BE SUPPORTED FROM COMM. WIRES
2) INSULATE S/A DUCT WHERE IT CROSSES EXHAUST DUCT IN LOBBY
3) PROVIDE REQUIRED AMOUNT OF SCREWS IN EXHAUST DUCT
4) PROVIDE RED LINE DRAWINGS OF CHANGES OF DUCT ROUTING PRIOR TO FINAL