Permit: T09CM01332

Parcel: 129120810


Addresses:

1014 E 27TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/09/2010 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
05/18/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
1. RISER HARDWARE TO BE 1/4" MINIMUM
2. A LISTED & APPROVED MAST BRACE KIT IS NEEDED
3. VERIFY GROUNDING ELECTRODE SYSTEM, GAS & WATER BONDS
5. FILL UNUSED OPENINGS IN PANEL
6. MAINTAIN WORKING CLEARANCES