Permit: T09CM01330

Parcel: 14044007D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) FINAL APPROVAL BASED ON EXPOSURE OF 10' SECTION OF U.G. PVC AND REPORT PROVIDED BY DARCOR PICTURES PROVIDED BY MOLLY OF ENVIORMENTAL SERVICES. THIS IS 2ND TIME UNDERGROUND RACEWAYS COVERED WITHOUT INSPECTIONS. NEXT TIME THIS HAPPENS ALL NEW WORK WILL BE EXPOSED
06/26/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTIONS PER JASON JAWORSKY UNTIL COVERING OF NEW WORK WITHOUT INSPECTIONS IS FIGURED OUT
06/26/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL GROUNDING ELECTRODE SYSTEM AT WELL SITES AS DISCUSSED
2) EXPOSE UNDERGROUND PVC PIPING JUST SOUTH OF WELL #1 FROM COUPLING TO COUPLING. NEED TO SEE MARKINGS ON PVC AND COUPLING CONNECTIONS
3) OK U.G. PULL BOXES
4) RECALL FOR RE-INSPECTION WHEN READY
06/24/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL UNDERGROUND COVERED WITHOUT INSPECTION
2. MAINTAIN PROPER DISTANCE FOR ANGLE PULLS 314.28
3. FINISH ELECTRICAL WORK