Permit: T09CM01329

Parcel: 132171280

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/24/2009 ELECTRIC - FINAL Approved CODE CORRECTIONS NOTED RICK HOLLANDER HAVE BEEN MADE. PER MY PERSONAL INSPECTION THIS EQUIPMENT MEETS NEC CODE REQUIREMENTS & PER THE INSPECTION DONE BY O. RENDON (MC-GETRICK ENGINEERING) THE EQUIPMENT HAS BEEN BUILT PER UL746-F. I DO NOT FIND THAT THERE ARE GROUNDS TO REQUIRE A NRTL LISTING AS AN ASSEMBLY FOR THIS EQUIPEMENT.
09/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/09/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/09/2009 ELECTRIC - FINAL Denied 1 NEED WORKING CELARANCES 110.26
2 BOND AS PER 250.97
3 CLEAN SURFACE UNDER LUGS 250.12
4 TIGHTEN LOOSE FITTINGS
5 VERIFY LISTING FOR EQUIPMENT 90.7, 110.3
6 ONLY ON CONDUCTOR PER LUG TERMINATION 110.14
7 FINISH SUPPORTING VDV CABLING 725.24
8 SECURE FIXTURES TO GRID 410.16, RELOCATE FIXTURE
9 REVISE PANEL DIRECTORIES PER 408.4
10 REVISE PLANS FOR PANEL & BREAKER ADDED - TAP NOT USED AND DELETION OF A/C SYSTEM