Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2009 | ELECTRIC - FINAL | Approved | CODE CORRECTIONS NOTED RICK HOLLANDER HAVE BEEN MADE. PER MY PERSONAL INSPECTION THIS EQUIPMENT MEETS NEC CODE REQUIREMENTS & PER THE INSPECTION DONE BY O. RENDON (MC-GETRICK ENGINEERING) THE EQUIPMENT HAS BEEN BUILT PER UL746-F. I DO NOT FIND THAT THERE ARE GROUNDS TO REQUIRE A NRTL LISTING AS AN ASSEMBLY FOR THIS EQUIPEMENT. | |
| 09/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/09/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/09/2009 | ELECTRIC - FINAL | Denied | 1 NEED WORKING CELARANCES 110.26 2 BOND AS PER 250.97 3 CLEAN SURFACE UNDER LUGS 250.12 4 TIGHTEN LOOSE FITTINGS 5 VERIFY LISTING FOR EQUIPMENT 90.7, 110.3 6 ONLY ON CONDUCTOR PER LUG TERMINATION 110.14 7 FINISH SUPPORTING VDV CABLING 725.24 8 SECURE FIXTURES TO GRID 410.16, RELOCATE FIXTURE 9 REVISE PANEL DIRECTORIES PER 408.4 10 REVISE PLANS FOR PANEL & BREAKER ADDED - TAP NOT USED AND DELETION OF A/C SYSTEM |