Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01328
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2009 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
06/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE ITEM #10 FROM PREVIOUS INSPECTION ON 6/9/09 |
|
06/09/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS IN GUTTER & PANELS 2. BLANK OPEN BREAKER POSITIONS IN PANEL 3. EM LIGHTING TO BE CONNECTED TO LIGHTING CIRCUIT IN AREA 4. HAVE PANEL COVERS REMOVED FOR NEXT INSPECTION 5. ABOVE CEILING NEVER APPROVED HAVE CEILINGS TILES REMOVED AND LADDER ON SITE 6. GROUNDING ELECTRODE SYSTEM CUT AND STOLEN INSTALL NEW GROUNDING ELECTRODE SYSTEM AND BOND BUILDING STEEL, GAS AND WATER PIPING 7. ADDRESS SERVICE & MARK "SERVICE DISCONNECT" 8. PORCELAIN KNOBS FOR SERVICE. NEED TO BE REANCHORED TO BUILDING 9. STRAP EMT ABOVE PANELS 10. TAP CONDUCTORS @ PANELS NOT PROPERLY PROTECTED - NEC 240.21 11. HAVE BREAKERS HIGHER THAN 6'7" NEC 240.24 12. BUSSING AT PANELS NOT PROPERLY PROTECTED |