Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2009 | FRAMING | Approved | IVRS - Inspection :* 1) NOTE: OLD GAS ? 2) CONDENSATE 3) TAPE DBL/SINGLE 4) TWO CONDENSATES REQUIRED 5) ONE COMB/RELIEF DUCT METHOD OK 6) RANGE USE 20 AMP BREAKER |
|
| 07/13/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ALL WIRING TO CODE 2) DISHWASHER ? CIRCUIT #13 PER PLAN 3) ALL LUMBER SOLE PLATES MUST BE TREATED LUMBER 4) FIREBLOCK DROPPED CEILINGS 5) JUNCTION BOX AT ENTRY NOT ACCESSIBLE 6) PROVIDE APPROVED CEILING FROM NOTES 7) SMOKE ALARM WIRING IN APPROVED BOXES INTERCONNECTED MINIMUM 36" FROM FORCED AIR REGISTERS 8) COMBUSTION AIR WATER HEATER ROOM EXTEND RELIEF LINE TO EXTERIOR 1" CLEARANCE 9) MAKE UP ALL EXHAUST FANS B-VENT |