Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM01306
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) PROVIDE ENGINEERS APPROVAL FOR ALTERNATE DUCT HANGER PRIOR TO FINAL |
|
09/11/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE BEADED COLLARS ON ALL CEILING DIFFUSERS |
|
09/03/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE BEADED COLLARS ON ALL SUPPLY AND RETURN DIFFUSERS -- OK PARTIAL TILES |
|
08/07/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE BUSHINGS WHERE STAT WIRE PENETRATES RETURN PLENIUMS 2) MOUNT STATS AT A.D.A. LIGHT 3) REPAIR INSULATION ON CONDENSATE DRAINS 4) SUSPENDED ROUGH DUCT OK TO INSULATE 5) SUPPLY AND EXHAUST IN RESTROOMS OK TO SHEETROCK 6) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR DUCT SMOKE DETECTORS 7) PLANS REQUIRE ALL THREAD TO SUPPORT DUCTING 8) PROVIDE A LETTER FROM ENGINEER IF USING A DIFFERENT METHOD |