Permit: T09CM01306

Parcel: 105102520


Addresses:

4206 N 1ST AV #120


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM01306

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) PROVIDE ENGINEERS APPROVAL FOR ALTERNATE DUCT HANGER PRIOR TO FINAL
09/11/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE BEADED COLLARS ON ALL CEILING DIFFUSERS
09/03/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE BEADED COLLARS ON ALL SUPPLY AND RETURN DIFFUSERS -- OK PARTIAL TILES
08/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE BUSHINGS WHERE STAT WIRE PENETRATES RETURN PLENIUMS
2) MOUNT STATS AT A.D.A. LIGHT
3) REPAIR INSULATION ON CONDENSATE DRAINS
4) SUSPENDED ROUGH DUCT OK TO INSULATE
5) SUPPLY AND EXHAUST IN RESTROOMS OK TO SHEETROCK
6) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR DUCT SMOKE DETECTORS
7) PLANS REQUIRE ALL THREAD TO SUPPORT DUCTING
8) PROVIDE A LETTER FROM ENGINEER IF USING A DIFFERENT METHOD